| Rating |
5 KVA TO 30 KVA |
| AC input |
415V + 15%, -20% Three Phase 4 Wire |
| Frequency |
50Hz + 6% |
| DC VOLTAGE |
72VDC TO 360VDC |
| Charging time |
15 Hours for 90% of full capacity |
| Charger type |
SMPS charger (IGBT Based) |
| INVERTER |
| Technology |
IGBT, High Frequency PWM |
| Output voltage |
400V / 415V AC three phase |
| Voltage regulation |
+2% for DC I/P Variation & O/P Load Variation |
| Frequency |
50Hz + 1% |
| Waveform |
Pure sine Wave |
| Harmonic Distortion |
Less Than 3% |
| Inverter Efficiency |
>90% for 360 VDC
>85% for 180 VDC |
| Power Factor |
0.8 |
| Over Load |
105% Countinuously
500% for 2 Sec. |
| Allowed Imbalance |
10% |
| Crest Factor |
4:1 |
| Transient Response |
+ 4% under full load change & corrected within 60 msec |
| Phase displacement |
120o + 1o |
| Audible Noise |
Less Than 45db at 1 meter |
| GENERAL |
| Operating Temperature |
0oC To 50oC |
| Humidity |
Max 95%, Non-Condensing |
PROTECTIONS
Output overload & short circuit, Output Under & Over voltage, DC Under & Over Voltage input under & over voltage, single phasing & phase unbalance |
| INDICATIONS & ALARMS |
| A) Mains on (R.Y.B.) |
LED Indication |
| B) Inverter on |
LED Indication |
| C) Battery Low |
LED Indication & alarm |
| D) Input Under Voltage |
Mains LED slow blinking |
| E) Input Over Voltage |
Mains LED fast blinking |
| F) Output Over load |
LED Indication & alarm |
| CHANGER OVER |
| A) Elector Mechanical - (switch Contactor) |
Provided as standard feature |
| B) Static Switch |
BI - Directional (Optional ) |
| ISOLATION POWER |
| Input |
MCB Provided |
| Output |
Switch,MCB(Optional) |
| Battery |
Fuse Link, MCB (Optional) |